房间:表面 50m² U0.5 + 10m² U1.8,室内 24°C/50%,室外 33°C/70%,V=120,ACH=0.5 围护传热 ΔT=(33-24)=9 K。Q_trans=50·0.5·9+10·1.8·9=225+162=387 W。显热渗风 Q_s=1.23·0.5·120·9≈664.2 W。潜热 ΔW 由含湿量差算出;Q_l=3010·0.5·120·ΔW(以代码为准)。总负荷=显热+潜热。{"result":"Cooling load estimate. ΔT=9 K, V=120 m³, ACH=0.5. Transmission Q_trans=387 W (2 surfaces), sensible infiltration Q_s=664.2 W, latent infiltration Q_l=2365.41 W. Total sensible=1051.2 W, total latent=2365.41 W. Total cooling load=3416.61 W.","metadata":{"input":{"surfaces":[{"area_m2":50,"U":0.5},{"area_m2":10,"U":1.8}],"areaUnit":"m2","indoorTemp":24,"outdoorTemp":33,"tempUnit":"°C","indoorRH":50,"outdoorRH":70,"volume":120,"ach":0.5},"result":{"transmissionLoad_W":387,"sensibleInfilLoad_W":664.2,"latentInfilLoad_W":2365.41,"totalSensibleLoad_W":1051.2,"totalLatentLoad_W":2365.41,"totalCoolingLoad_W":3416.61,"deltaT_K":9,"humidityRatioDiff":0.01309753,"surfaceCount":2,"individualSurfaces":[{"area_m2":50,"U":0.5,"load_W":225},{"area_m2":10,"U":1.8,"load_W":162}]}}}
同一房间用 ft²:表面 538ft² U0.5 + 108ft² U1.8(≈50m²/10m²),其余相同,V=120 m³,ACH=0.5 同一物理房间,面积以 ft² 输入(内部换算为 m²)。结果与 m² 输入一致(以代码为准)。{"result":"Cooling load estimate. ΔT=9 K, V=120 m³, ACH=0.5. Transmission Q_trans=387.46 W (2 surfaces), sensible infiltration Q_s=664.2 W, latent infiltration Q_l=2365.41 W. Total sensible=1051.66 W, total latent=2365.41 W. Total cooling load=3417.08 W.","metadata":{"input":{"surfaces":[{"area_m2":49.98,"U":0.5},{"area_m2":10.03,"U":1.8}],"areaUnit":"ft2","indoorTemp":24,"outdoorTemp":33,"tempUnit":"°C","indoorRH":50,"outdoorRH":70,"volume":120,"ach":0.5},"result":{"transmissionLoad_W":387.46,"sensibleInfilLoad_W":664.2,"latentInfilLoad_W":2365.41,"totalSensibleLoad_W":1051.66,"totalLatentLoad_W":2365.41,"totalCoolingLoad_W":3417.08,"deltaT_K":9,"humidityRatioDiff":0.01309753,"surfaceCount":2,"individualSurfaces":[{"area_m2":49.98,"U":0.5,"load_W":224.92},{"area_m2":10.03,"U":1.8,"load_W":162.54}]}}}