1. 25 °C air at 50% relative humidity
HVAC engineerBackground
An HVAC engineer needs the main moist-air properties for air at 25 °C and standard atmospheric pressure.
Problem
Convert the relative-humidity reading into humidity ratio, dew point, wet bulb, enthalpy, and specific volume.
How to use
Enter 25 as the dry-bulb temperature, select °C, choose Relative Humidity φ, and enter 50. Use 101.325 kPa pressure.
Temperature: 25 °C; humidity input: RH; humidity value: 50%; pressure: 101.325 kPa; humidity-ratio unit: g/kg.Outcome
The result is approximately W=9.876 g/kg, φ=50%, dew point=13.86 °C, wet bulb=17.89 °C, enthalpy=50.31 kJ/kg dry air, and specific volume=0.8578 m³/kg dry air.