1. Cooling coil capacity from relative humidity
HVAC engineerBackground
An engineer is checking an AHU cooling coil with 2.5 kg/s of dry-air flow. The entering air is 27 °C and 50% RH, while the leaving air is 14 °C and 90% RH.
Problem
Determine the coil's total, sensible, and latent capacity and calculate its SHR.
How to use
Enter 2.5 kg/s, select relative humidity for both states, enter 27 °C and 50% for the entering air, then 14 °C and 90% for the leaving air. Select kW as the capacity unit.
mda=2.5; flowUnit=kg/s; t1=27; h1Input=relative humidity; h1Value=50; t2=14; h2Input=relative humidity; h2Value=90; capacityUnit=kWOutcome
The calculator returns approximately 47.01 kW total capacity, 33.31 kW sensible capacity, 13.70 kW latent capacity, and an SHR of 0.709.