1. ASHRAE 62.1 office airflow estimate
HVAC designerBackground
An office has 20 occupants and a 100 m² floor area. The design uses a per-person rate of 2.5 L/s-person, an area rate of 0.3 L/s-m², and Ez of 1.0.
Problem
Determine the required zone supply airflow and express it in common ventilation units.
How to use
Select ASHRAE 62.1 mode and enter the occupant count, people rate, floor area, area rate, and zone effectiveness.
P=20; Rp=2.5 L/s-person; A=100 m²; Ra=0.3 L/s-m²; Ez=1.0Outcome
The people component is 50 L/s and the area component is 30 L/s. The required airflow is 80 L/s, equal to 288 m³/h or 169.51 CFM.