1. Step-Down Transformer Verification
Electrical Design EngineerBackground
Designing a control panel transformer that steps down 230V mains voltage to 57.5V for auxiliary circuits.
Problem
Need to verify the turns ratio and determine the primary current draw when the secondary load draws 10A.
How to use
Select 'Turns' mode, enter 1000 for Primary Turns (N1), 250 for Secondary Turns (N2), 230 for Primary Voltage (V1), and 10 for Secondary Current (I2).
mode: turns, N1: 1000, N2: 250, V1: 230, I2: 10, decimalPlaces: 4Outcome
Calculates a turns ratio of 4.0000, secondary voltage of 57.5V, primary current of 2.5A, and confirms power balance at 575W.