1. Sizing Cable for a Hot Plant Environment
Electrical Design EngineerBackground
An engineer needs to run a power line using a 16 mm² XLPE cable buried directly in the ground (Method C) where the ambient soil/air temperature reaches 40 °C.
Problem
Determine the corrected allowable ampacity considering the high ambient temperature and burial installation.
How to use
Select '16' for Cross-Section, 'XLPE' for Insulation, 'C — Direct in ground' for Installation Method, and set the Ambient Temperature to 40 °C.
Outcome
The calculator applies a temperature factor of 0.91 and an installation factor of 0.85 to the 96 A base current, resulting in a safe corrected ampacity of approximately 74.49 A.