1. Office winter comfort assessment
Building engineerBackground
A building engineer is reviewing a winter office condition with equal air and mean radiant temperatures, moderate humidity, seated office activity, and business clothing.
Problem
Estimate whether occupants are likely to feel neutral and determine the predicted dissatisfied percentage.
How to use
Enter Ta=22 °C, Tr=22 °C, relative air velocity=0.1 m/s, RH=50%, met=1.2, clo=1.0, and external work=0.
{"ta":22,"tr":22,"tempUnit":"°C","var":0.1,"rh":50,"met":1.2,"clo":1.0,"work":0,"decimalPlaces":3}Outcome
The result is PMV=-0.025 with a Neutral label and PPD=5.01%.