Ventilation Rate Calculator (People / Area / Contaminant)
Compute the required outdoor / supply ventilation rate. ASHRAE 62.1 ventilation-rate procedure: people component Vpz = Rp·P, area component Vaz = Ra·A, breathing-zone outdoor air Vbz = Vpz + Vaz, zone supply airflow Voz = Vbz / Ez. Three modes: ASHRAE 62.1 (people + area), per-person rate (P × Rp), or contaminant dilution (Q = G / (C_acc − C_sup), where G can be mg/s, mg/h, or L/s of gas and concentrations mg/m³ or ppm). Results reported in L/s, m³/h, and CFM.
Floor area A, in the selected Area Unit. Used in 'ashrae' mode.
areaUnit
select
No
—
ra
number
No
Outdoor air rate per unit area Ra, in the selected Area Rate Unit. Used in 'ashrae' mode.
raUnit
select
No
—
ez
number
No
Zone air distribution effectiveness Ez (0.1–2). Default 1.0. Typical: ceiling supply cool air = 1.0, warm air = 0.8, floor supply = 1.0. Used in 'ashrae' mode.
gGeneration
number
No
Pollutant generation rate G, in the selected Pollutant Unit. Used in 'contaminant' mode. For CO₂: ~0.005 L/s per person at rest.
gUnit
select
No
—
cAccept
number
No
Acceptable (target) concentration C_acc, in the selected Concentration Unit. Used in 'contaminant' mode.
cSupply
number
No
Supply (outdoor) air concentration C_sup, in the selected Concentration Unit. Used in 'contaminant' mode.
cUnit
select
No
—
molarMass
number
No
Pollutant molar mass M (g/mol), used to convert ppm ↔ mg/m³. Default 44.01 (CO₂). Only used when Concentration Unit = ppm in contaminant mode.